14 part numbersTeSys Deca Contactors
Schneider Electric TeSys Deca (TeSys D) LC1D contactors, 9 A to 95 A AC-3 at up to 440 V, with 220 V AC (M7) or 24 V DC (BD) coils and 1 NO + 1 NC auxiliary contacts built in.
- TeSys Deca
- TeSys D
- LC1D
- LC1D09M7

GV2ME thermal-magnetic motor circuit breakers from 0.63 A to 32 A with push-button operation.
Price on request — quoted per part number
Quotes within 24 hours on working days
The TeSys GV2ME is the familiar push-button motor circuit breaker found in countless Pakistani panels. It protects a motor against short circuit, overload and phase loss, and it isolates it with a clear start/stop push-button — replacing fuses and a separate overload relay in one device.
Each GV2ME covers a setting range; the code number rises with the current. GV2ME08 covers 2.5–4 A, GV2ME14 6–10 A, GV2ME22 20–25 A and GV2ME32 24–32 A. Choose the breaker whose range includes the motor's full-load current and set the dial to it. GVAE11 auxiliary contacts (1 NO + 1 NC) give the PLC a trip or on/off signal.
GV2 breakers combine with TeSys D contactors to build compact starters for remote control. We supply the full GV2ME range and its accessories — send the motor current or the reference of your old breaker and we match it.
The codes our customers ask for most. Add the ones you need to your quote list — or send any other TeSys GV2 Motor Circuit Breakers variant and we check it for you.
| Part number | Description | Key spec | Quote |
|---|---|---|---|
| GV2ME05 | Motor circuit breaker 3P, 0.63–1 A, thermal-magnetic | 0.63–1 A | |
| GV2ME06 | Motor circuit breaker 3P, 1–1.6 A, thermal-magnetic | 1–1.6 A | |
| GV2ME07 | Motor circuit breaker 3P, 1.6–2.5 A, thermal-magnetic | 1.6–2.5 A | |
| GV2ME08 | Motor circuit breaker 3P, 2.5–4 A, thermal-magnetic | 2.5–4 A | |
| GV2ME10 | Motor circuit breaker 3P, 4–6.3 A, thermal-magnetic | 4–6.3 A | |
| GV2ME14 | Motor circuit breaker 3P, 6–10 A, thermal-magnetic | 6–10 A | |
| GV2ME16 | Motor circuit breaker 3P, 9–14 A, thermal-magnetic | 9–14 A | |
| GV2ME20 | Motor circuit breaker 3P, 13–18 A, thermal-magnetic | 13–18 A | |
| GV2ME21 | Motor circuit breaker 3P, 17–23 A, thermal-magnetic | 17–23 A | |
| GV2ME22 | Motor circuit breaker 3P, 20–25 A, thermal-magnetic | 20–25 A | |
| GV2ME32 | Motor circuit breaker 3P, 24–32 A, thermal-magnetic | 24–32 A | |
| GVAE11 | Auxiliary contact 1 NO + 1 NC for GV2/GV3 | Accessory |
Send a photo of the Schneider Electric part’s nameplate or label. Our engineers identify it and reply with the exact code and a quotation.
Schneider Electric TeSys GV2 Motor Circuit Breakers prices are quoted per part number. The final price depends on the exact code, the quantity and the exchange rate on the day, so we send an itemised quotation with prices, lead time and terms for every line.
To get a price, add part numbers from the table to your quote list, message us on WhatsApp, or send a photo of the nameplate. We deliver across Pakistan — Karachi, Lahore, Faisalabad, Islamabad and industrial areas in between.
Applications
Protection of small and medium motors in MCCs.
Direct start/stop of pumps, fans and conveyors.
Upgrading fuse-based starters to breaker protection.
More from Schneider Electric
14 part numbersSchneider Electric TeSys Deca (TeSys D) LC1D contactors, 9 A to 95 A AC-3 at up to 440 V, with 220 V AC (M7) or 24 V DC (BD) coils and 1 NO + 1 NC auxiliary contacts built in.
12 part numbersSchneider Electric Altivar Machine ATV320 variable speed drives, compact format: 1-phase 200–240 V from 0.37 to 2.2 kW and 3-phase 380–500 V from 0.75 to 15 kW, for packaging, handling and process machines.
13 part numbersSchneider Electric TeSys LRD thermal overload relays, class 10A, with setting ranges from 1 A to 65 A, mounting directly under TeSys D contactors for motor overload and phase-loss protection.
9 part numbersSchneider Electric Altivar Easy ATV310 variable speed drives for 3-phase 380–460 V motors from 0.75 kW to 15 kW — simple, robust drives for pumps, fans, conveyors and mixers.
17 part numbersSchneider Electric Acti9 iC60N miniature circuit breakers (A9F44 references), C curve, 1, 2, 3 and 4-pole from 6 A to 63 A, for distribution boards and control panels.
12 part numbersSchneider Electric Harmony XB5 (plastic) and XB4 (metal) Ø22 mm control units: flush push buttons, emergency stops, selector switches and LED pilot lights for control panels and machines.
FAQs
A 4 kW 400 V motor draws about 8 A, so the GV2ME14 (6–10 A) fits. Set the dial to the nameplate current.
Yes — fit a GVAE11 auxiliary contact (1 NO + 1 NC) and wire it to the PLC.
Prices depend on the exact part number, quantity and current exchange rate. Send us the codes you need and we reply with an itemised quotation. Quotes within 24 hours on working days.
The table shows the codes we are asked for most; we offer the other TeSys GV2 Motor Circuit Breakers variants too. Send the part number or a photo of the nameplate and we reply with a quotation.
Yes. We offer genuine Schneider Electric products only — no copies, and no substitutes without your approval.
Talk to an engineer
Send the part numbers and quantities, a BOM or a nameplate photo. We check availability and reply with an itemised quotation.
Quotes within 24 hours on working days
Mon–Sat, 10:00 am – 8:00 pm
Schneider Electric and related names, product images and logos are trademarks of their respective owner, used on this page for identification only. See our trademark notice.